Wiring for Single Family
Dwellings
INDEX
INTRODUCTION
ELECTRIC SERVICE
BRANCH CIRCUIT WIRING
REQUIRED BRANCH CIRCUITS
REQUIRED RECEPTACLE OUTLETS
REQUIRED LIGHTING OUTLETS
GROUND FAULT PROTECTION
REQUIRED DISCONNECTION MEANS
CONDUCTOR FILL
EQUIPMENT GROUNDING CONDUCTOR MAKE-UP
ELECTRIC HEAT CIRCUITRY
ROUGH-IN INSPECTION
FINAL INSPECTION
DOWNLOAD THIS INFORMATION IN ENGLISH OR SPANISH
INTRODUCTION
DO
NOT HESITATE TO ASK YOUR INSPECTOR QUESTIONS
This
guideline has been prepared to assist the lay person in complying with the
requirements of all Longmont adopted Electrical Codes, and assure the installation
of a safe and reliable electrical system. This guideline is not inclusive
for every installation and is not an instruction manual.
Along
with meeting NEC requirements, the permit and inspection process defined by
ordinance must be followed. If for some reason, the job does not meet the
requirements of the NEC and an extra visit is necessary, a re-inspection fee
may be required before the inspector can return.
See
the currently adopted codes and local amendments
on our web site. In addition, check with Longmont Power and Communications
(303-651-8386) for their requirements.
Top
ELECTRIC
SERVICE
The service equipment must be large enough to supply the connected load, which
is calculated using Article 220 of the NEC. The most common sizes of residential
service equipment are 100, 125, 150, and 200 amperes. The minimum wire size
for service entrance conductors are listed below:
Conductor
Types and Sizes for 120/240-Volt, 3-Wire, Single-Phase Dwelling Services
RH,
RHH, RHW, RHW-2, THHN, THHW, THW, THWN, XHHW, USE*
*Type
"USE" (Underground Service Entrance) conductors are not permitted
to enter a building unless they are triple rated with the additional markings
RHH and RHW.
| COPPER |
ALUMINUM
AND COPPER CLAD ALUMINUM |
SERVICE
RATING IN AMPS |
| AWG
|
AWG |
|
| 4 |
2 |
100 |
| 3 |
1 |
110 |
| 2 |
1/0 |
125
(min for new home) |
| 1 |
2/0 |
150 |
| 1/0 |
3/0 |
175 |
| 2/0 |
4/0 |
200 |
The
service equipment must be grounded in accordance with Article 250 of the NEC,
which, in general, says the neutral must be bonded to the service enclosure
and the grounding electrode system as defined in Article 250-50.
The main service equipment panel shall be mounted either outside or inside
the dwelling, as near as possible to the point of entrance of the service
conductors to the building. All service equipment and electrical panels shall
have a clear area 30" wide and 36" deep in front. This clear area
must extend from floor to ceiling with no intrusions from other equipment,
cabinets, counters, appliances, etc. Panels are NOT permitted in clothes closets
or bathrooms.
In the main service equipment, the neutral and equipment grounding conductors
are bonded together; in sub-panels, the neutral is isolated from ground. The
cold water pipe and the supplementary grounding electrode (ground rod), are
also bonded to the neutral at the service equipment. The electric meter enclosure
should be mounted at 5' 6" above finish grade, at the center of the meter
opening. Overhead drops should have a clearance of 10' above finish grade
to the bottom of the drip loop.
Top
BRANCH
CIRCUIT WIRING
Type NM cable (also known as romex) is the wiring method most frequently used
in residential dwellings. Type NM cable must have a 90 degree conductor insulation
rating, which is designated on the cable sheath by a "B".
Type NM-B #12/2 w/ground and #14/2 w/ground are used for lighting and general
purpose receptacle circuits. #10/2 w/ground is commonly used for electric
water heaters, #10/3 w/ground for electric dryers, and #8/3 w/ground &
#6/3 w/ground for ranges and wall mounted ovens. Type "SER" cable
with an insulated neutral is permitted for electrical ranges, wall ovens and
dryers.
The cables must be protected by over-current devices (circuit breakers), which
do not exceed their rated ampacity. The rated ampacities for cable types are
listed below:
| COPPER NM CABLE |
TYPE S.E. AND S.E.R. ALUMINUM
CABLE |
| 15 amperes for #14 |
40 amperes for #8 |
| 20 amperes for # 12 |
50 amperes for #6 |
| 30 amperes for #10 |
|
| 40 amperes for #8 |
|
| 50 amperes for #6 |
|
It
is important to note that if you begin a circuit with #12, you must use this
same wire size throughout. You can not mix different wire sizes on
the same branch circuit.
Type NM cable must be stapled within 12" of metal boxes, 8" of plastic
boxes and every 4½ feet thereafter. Proper connectors must be used
where NM cable enters metal cabinets, boxes or panel boards.
When Type NM cable is installed parallel to framing members, or in bored holes,
it shall be located at least 1¼" from the nearest edge of the
framing member, where nails or screws may penetrate the cables. If this distance
cannot be maintained, the cable shall be protected by a steel plate or sleeve
at least 1/16" thick. Article 300-4(d).
Cable or raceway-type wiring methods installed in a groove, to be covered
by paneling, carpeting, or similar finish, shall be protected by a 1/16-inch
steel plate, sleeve, or equivalent, or must be recessed in the groove 1 ¼-inch
for the full length of the groove in which the cable or raceway is installed.
Exception: Raceways as covered in articles 345,346, 347, and 348. Article
300-4(e).
Ceiling mounted paddle fans weighing 35 pounds or less may be supported by
outlet boxes identified for such use. Fans weighing more than 35 pounds must
be supported independently of the box. Article 422-18.
Top
REQUIRED BRANCH CIRCUITS
a.
Small Appliance Branch Circuits - The NEC requires a minimum of two 20 ampere
branch circuits to feed receptacle outlets for small appliance loads, including
refrigeration equipment in the kitchen, pantry, breakfast room, and dining
room. These circuits, whether two or more are used, shall not supply anything
other than receptacles in these areas. Lighting outlets and built-in appliances
such as garbage disposals, hood fans, dishwashers, and trash compactors
are not permitted on these circuits. Kitchen counter top receptacles must
be supplied by at least two small appliance branch circuits. See electrical
code amendments.
b. Laundry Branch Circuit - One 20 amp branch circuit must be provided for
the laundry. This circuit is limited to receptacles within the laundry room.
No other outlets are permitted on this circuit.
c. Bathroom Receptacles - At least one 20 amp circuit for bathroom receptacle
outlets shall be supplied, such circuits may have no other outlets.
d. Exception: Where the 20 ampere circuit supplies a single bathroom, outlets
for other equipment within the same bathroom shall be permitted to be supplied
in accordance with 210-23a. (This circuit would not be used to supply a
whirlpool bath or a hot tub!)
e. Central Heat - Central heating equipment shall be supplied by an individual
branch circuit.
f. General Lighting Branch Circuits - Shall be computed on a three watts
per square foot basis. You may wire up to 600 square feet of living area
on a 15 ampere branch circuit or up to 800 square feet on a 20 ampere circuit.
These branch circuits may supply lighting outlets in all areas of the dwelling
and receptacle outlets, other than those covered in (a) - (d) above.
Top
REQUIRED
RECEPTACLE OUTLETS
a.
At least one outlet shall be installed in bathrooms within 36 inches of
the outside edge of each basin. The receptacle outlet shall be located on
a wall that is adjacent to the basin location.
b. At least one outlet in every attached garage, and one outlet in every
detached garage with electric power.
c. At least two outlets installed outdoors, one on the front and one on
the back of the dwelling, accessible at grade level.
d. At least one receptacle must be installed in the unfinished portion of
the basement. This receptacle is in addition to any receptacles that may
be installed for laundry or other specific purposes.
e. In every kitchen, family room, dining room, living room, parlor, library,
den, sun room, bedroom, recreation room or similar room, or area of dwelling
units, receptacle outlets shall be installed so that no point along the
floor line in any wall space is more than six feet horizontally, measured
from an outlet in that space, including any wall space two feet or more
in width, and excluding only that space occupied by sliding panels in exterior
walls. The wall space afforded by fixed room dividers, such as freestanding
bar-type counters or railings, shall be included in the six foot measurement.
No outlets may be installed over an electric baseboard heater.
f. In kitchens and dining areas, a receptacle outlet shall be installed
at each counter space wider than 12". Countertop receptacles shall
be installed so that no point along the wall line is more than 24"
measured horizontally from a receptacle outlet in that space. Peninsular
bars and islands 12" or wider shall have at least one receptacle.
g. Receptacles installed in the floor must use a box-receptacle combination
designed specifically for that purpose. Receptacles installed in the floor
within 18" of the wall may be used in place of wall mounted receptacles.
A receptacle outlet is required in any dwelling unit hallway that is ten
feet or more in length.
h. At least one 15 or 20 ampere, 125 volt GFCI protected receptacle must
be installed at an indoor spa or hot tub location, not closer than five
feet from the inside wall of the unit and not more than ten feet away from
it. Light fixtures, outlets and ceiling fans over spas and hot tubs shall
be a minimum of 7'6" above the maximum water level. Outdoors spa or
hot tubs have the same requirements as a swimming pool. Check with your
inspector for those requirements.
i. Dwelling Unit Bedrooms. All branch circuits that supply 125 volt, single
phase, 15- and 20- ampere outlets installed in dwelling unit bedrooms shall
be protected by an arc-fault circuit interrupter(s).
Arc-Fault Circuit-Interrupter Protection - Definition. An arc-fault circuit
interrupter is a device intended to provide protection from the effects
of arc faults by recognizing characteristics unique to arcing and by functioning
to de-energize the circuit when an arc fault is detected.
Top
REQUIRED
LIGHTING OUTLETS
a.
At least one wall switch-controlled lighting outlet shall be installed in
every habitable room; in bathrooms, hallways, stairways, attached garages,
detached garages with electric power, and at outdoor entrances or exits.
The lighting outlet for interior stairways shall have a wall switch at each
floor level where the difference between floor levels is six steps or more.
b.
At least one wall switch controlled lighting outlet shall be installed in
an attic, under-floor space, utility room, and basement, where these spaces
are used for storage or contain equipment requiring servicing. The switch
shall be located at the point of entry to these areas, and the lighting
outlet located at or near the equipment requiring servicing.
Identification of switch leg: Circuits of 50 Volts or More. The use of insulation
that is white or natural gray or that has three continuous white stripes
for other than a grounded conductor for circuits of 50 volts or more shall
be permitted if part of a cable assembly and where the insulation is permanently
re-identified to indicate its use as an ungrounded conductor, by painting
or other effective means at its termination, and at each location where
the conductor is visible and accessible.
Top
GROUND FAULT PROTECTION
All
receptacles listed below must be protected by a ground fault circuit interrupter:
a.
Bathrooms receptacles.
b. All outdoor receptacles.
c. Garage receptacles except those not readily accessible such as ceiling
mounted receptacles or single receptacles in dedicated spaces for appliances.
d. Kitchen receptacles that serve counter top surfaces.
e. Counter top receptacles within 6 feet of a wet bar sink.
f. All receptacles in an unfinished basement or crawl space at or below
grade, with these exceptions:
g. Single receptacle within a dedicated location and identified for specific
use by a cord and plug connected appliance.
h. Single receptacle serving a permanently installed sump pump.
i. Hydro-massage bath tubs.
j. Spas and Hot tubs, water features and associated electrical components.
Top
REQUIRED DISCONNECTING MEANS
Disconnects
are required insight of the following equipment:
a.
Electric hot water heaters.
b. Central heating equipment (furnaces, boilers).
c. Spas, hot tubs and water features.
d. Hydro-massage bath tubs.
e. Air conditioners
Top
CONDUCTOR
FILL
Outlet
and junction boxes shall be of sufficient size to provide free space for all
conductors and devices enclosed in the box. All outlet boxes have a specific
volume, measured in cubic inches. For example, if you have two #12/2, with
ground NM-B cables entering a box with one duplex receptacle, you would need
a box with a minimum volume of 15.75 cubic inches. Each #12 that enters the
box needs 2.25 cubic inches with the exception of the grounding conductor
which requires one 2.25 cubic inch for all of the grounds. Also, each strap
containing one or more devices is counted as the equivalent of two conductors;
therefore, 2.25 x 7 = 15.75.
VOLUME
REQUIRED PER CONDUCTOR:
· #6 - 5 cubic inches
· #8 - 3 cubic inches
· #10 -2.5 cubic inches
· #12 -2.25 cubic inches
· #14 - 2 cubic inches
Top
EQUIPMENT
GROUNDING CONDUCTOR MAKE-UP
All equipment grounding conductors must be connected together with solder-less
pressure connectors such as wire-nuts or crimp sleeves, leaving sufficient
extra conductor for attachment to the metal box and/or device. When crimp
type connectors are used, they must be crimped using the tool recommended
by the manufacturer.
Please note that all metal junction and outlet boxes must be grounded by attaching
the equipment grounding conductor out of the NM cable to the metal box using
an approved screw or grounding clip. When circuit conductors are made up,
six inches of free conductor measured from the back of the box, must be left
for use in make-up and for the attachment of devices.
Return
to Index
ELECTRIC
HEAT CIRCUITRY
Electric heat may be installed on 15, 20, or 30 amp branch circuits. Listed
below is the maximum wattage that may be installed on each size branch circuit.
(All circuits are figured at 240 v):
·
15A - 2,880 watts maximum
· 20A - 3,840 watts maximum
· 30A - 5,760 watts maximum
For
example, if you are installing baseboard heaters which are rated 250 watts
a linear foot, you could install 15 feet on a 20 amp, 240 volt circuit. 250W
x 15 = 3,750 watts.
Top
ROUGH-IN
INSPECTION
At the time you call for rough-in inspection, you should have all wire pulled,
stapled properly, and all splices made up and ready to accept devices and
fixtures. Please DO NOT install any devices or cover any wiring with insulation
or wall coverings, i.e., drywall or paneling. Requirements of # 9 above must
be completed prior to the rough inspection.
The building code requires hard wired battery backup smoke detectors, one
on each level, one in the hallway or area serving a sleeping room and one
in each sleeping room. Additionally in areas where the ceiling height changes
24" or more on the same level another smoke detector must be installed
in the upper ceiling level. Check the manufacture's installation instructions
for smoke detectors placement. For remodel projects check with the electrical
inspector for smoke detector requirements.
Top
FINAL
INSPECTION
The electrical installation should be complete at the time of request. All
devices and fixtures installed, service equipment complete, and labeled properly.
All wiring shall be free from short circuits, ground faults and open circuits.
All light fixtures are required to be grounded along with light switches that
are within five feet of a grounded object.
Top
DOWNLOAD
THIS INFORMATION
IMPORTANT:
You MUST have the Adobe Acrobat Reader
on your system prior to selecting the report in order to be able to view these
files.
Top
Last Updated: 11/14/07
-->